Quick Start for Experienced Users

This chapter can help you to get started using the SLC 500 Modular Processors. We base the procedures here on the assumption that you have an understanding of SLC 500 products. You should understand electronic process control and be able to interpret the ladder logic instructions required to generate the electronic signals that control your application.

Because it is a start-up guide for experienced users, this chapter does not contain detailed explanations about the procedures listed. It does, however, reference other chapters in this book where you can get more information. If you have any questions or are unfamiliar with the terms used or concepts presented in the procedural steps, always read the referenced chapters and other recommended documentation before trying to apply the information

This chapter:

  • tells you what tools and equipment you need.
  • lists how to install your chassis.
  • lists how to install and wire your power supply.
  • lists how to install and apply power to your processor.
  • lists how to establish communication with the processor.
  • describes how to return the SLC 5/03, SLC 5/04, and SLC 5/05
  • processors to initial factory conditions if required.
  • Publication 1747-UM011G-EN-P – June 2008
  • 16 Quick Start for Experienced Users

Required Tools and Equipment

Have the following tools and equipment ready:

  • Medium blade screwdriver
  • Programming equipment
  • Compatible communication cable and/or interface (The table

below indicates with an X, which cables are compatible with the SLC 5/01 through 5/05 processors.)

Procedures

Network Interface Processor

SLC 5/01 SLC 5/02 SLC 5/03 SLC 5/04 SLC 5/05

  • 1747-UIC X(1)
  • (1) Requires 1747-C13 cable.
  • X(1) X(1)(4)
  • (4) Requires 1747-CP3 cable.
  • X(4) X(4)
  • 1747-PIC X X X
  • 1747-CP3 X X X
  • 1784-PKTX(D) X(2)
  • (2) Requires 1784-CP14 cable.
  • X(2) X(2) X
  • 1784-PCMK X(3)
  • (3) Requires 1784-PCM4 cable.
  • X(3) X(3) X(5)
  • (5) Requires 1784-PCM6 cable.
  • 10/100Base-T Ethernet X
  1. Check the contents of the shipping box. Reference

Unpack the shipping boxes making sure that the contents include:

  • SLC 500 modular processor

– installation instructions (publication 1747-IN009)

  • SLC 500 modular chassis (catalog numbers 1746-A4, 1746-A7, 1746-A10, or

1746-A13)

– installation instructions (publication 1746-IN016)

  • SLC 500 modular power supplies (catalog numbers 1746-P1, 1746-P2,

1746-P3, 1746-P4, 1746-P5, 1746-P6, or 1746-P7)

– installation instructions (publication 1746-IN004)

If the contents are incomplete, call your local Rockwell Automation representative for assistance.